, via cable lugs ferrules) the type terminal blocks used.wago.3 9 Dimensions based 6. WAGO recommends gas-tight tinned copper ferrules tinned copper pin terminals when connecting fine-stranded conductors terminal blocks corrosive atmospheres.1 for output terminal blocks between isolated intrinsically safe circuits (d2 mm) and between intrinsi- cally safe circuits and non-intrinsically safe circuits (d3 mm) 10 Where required .43 www. Legend: 1 Chassis 2 Load 3 Non-intrinsically safe circuit defined Um 4 Portion intrinsically safe circuit, item not intrinsically safe 5 Intrinsically safe circuit 6 Dimensions for which Table applies 7 Dimensions for which general industrial standards apply 8 Dimensions per 7.g.2.com 1 1 9 9 2 2 10 3 10 6 7 8 9 4 5 WAGO Rail-Mount Terminal Block Systems Technical Information for Applications Figure Isolation examples for conductive parts In accordance with DIN 60079-14 (VDE 0165-1), intrinsically safe circuits, the ends stranded and fine-stranded conductors must be protected against splaying (e. Soldering alone not sufficient. The conductor entry funnels WAGO PCB terminal blocks fulfill this requirement