Technical Section WAGO

| Kategorie: Leták / Datasheet Firemní tiskovina  | Tento dokument chci!

Vydal: WAGO Elektro spol. s r.o.

Strana 36 z 44

Jak získat tento dokument?






Poznámky redaktora
Zone 1 Area which explosive gas atmosphere is likely occur periodically occasion- ally during normal operation.wago. explosive atmosphere mixture flammable sub- stances the form gases, vapors mixtures with air under atmospheric conditions critically mixed ratios such that excessive high tempera- ture, arcs sparks may cause explosion. Zone 2: Area which explosive gas atmosphere is unlikely occur during normal opera- tion; does occur, then temporarily.com Zone 2 Zone Zone 0 Zone 0 Zone 1 Zone 1 Zone 22 Zone 21 Zone 20 WAGO Rail-Mount Terminal Block Systems Technical Information for Applications Harzardous Areas Hazardous areas are zones which the atmo- sphere may become explosive. EN 60079-10-1/EN 60079-10-2 and all other well-known standards rank hazardous areas according the likelihood the occurrence of explosive atmosphere into the following zones: Hazardous areas due explosive gases, vapors and mists: Zone 0 Area which explosive gas atmosphere is present continuously, for long periods or frequently. Zone 21 Area which explosive dust atmo- sphere due dust/air mixtures likely to occur occasionally during normal opera- tion. Hazardous areas due explosive dust/air mixtures: Zone 20 Area which explosive dust atmo- sphere due dust/air mixtures present continuously, for long periods fre- quently. Zone 22 Area which explosive dust atmo- sphere due flammable dust/air mixtures is unlikely occur during normal opera- tion; but occurs, then only for short period time. .35 www