Lightning protection guide by OBO

| Kategorie: Katalog  |

Last revision 2020

Vydal: OBO BETTERMANN s. r. o. Autor: OBO BETTERMANN

Strana 60 z 288

Jak získat tento dokument?






Poznámky redaktora
Risk level (LPL light- ning protection level) Radius rolling sphere Smallest peak current value Max. Note Lateral impacts can occur any building structures higher than the radius the rolling sphere. The rolling sphere method allows the installation di- vided into different external lightning protection zones (LPZs) "lightning protection levels" (LPLs): LPZ 0A Hazards from direct lightning strikes and the entire electromagnetic field the lightning. For example, buildings lightning protection class the ball touches surfaces and points that buildings lightning protection class II (or III IV) would still the protected area. However, the probability lateral impact negligible on building structures with height less than m. Rolling sphere method and the resulting lightning protec- tion zones (LPZs) TBS Blitzschutz-Leitfaden 2018 / en / 2020/01/10 14:42:40 14:42:40 (LLExport_02613) / 2020/01/10 14:42:54 14:42:54 60 Chapter The external lightning protection system . peak current value kA I 200 II 150 III 150 IV 100 Radius rolling sphere for different lightning protection classes Modern CAD programs can reproduce the rolling sphere rolling over the entire installation that is to protected. LPZ 0B Protected against direct lightning strikes, but risk from the entire electric field the lightning