Lightning protection guide by OBO

| Kategorie: Katalog  |

Last revision 2020

Vydal: OBO BETTERMANN s. r. o. Autor: OBO BETTERMANN

Strana 220 z 288

Jak získat tento dokument?






Poznámky redaktora
TBS Blitzschutz-Leitfaden 2018 / en / 2020/01/10 14:42:40 14:42:40 (LLExport_02613) / 2020/01/10 14:42:54 14:42:54 220 Chapter The internal lightning protection system . Lightning current can also enter the building via the telecommu- nications cable. the case light- ning strike, passes into the cable directly, this is known galvanic coupling. If lightning strikes and the lightning current flows into an air-termination rod and earth via the external lightning protection system, approximately 50% the lightning current enters the building via the building’s equipotential bonding system and hence couples gal- vanically.External lightning protection system Earthing system Main earthing busbar Transmitter Data cable carrying lightning current Galvanic coupling into data cable via the external lightning protection system "Galvanic coupling" When lightning current, e. metal rodent guard can turn even an EMC-insensitive fibre optic cable into conductor of lightning current. Coupled lightning currents are not always due the external lightning protection system: principle, any external cable that ends the house can couple light- ning currents, for example, strike substation or an exposed cable connected the house.g