addition, galvanic element
is created, which accelerates corrosion the contact
surface.
The following figure shows the use bimetal connect-
ors copper gutter which aluminium round
conductor attached. connection between two different materi-
als that are not recommended joined re-
quired, bi-metal connectors can used. Points increased risk cor-
rosion, such insertion points into the concrete or
soil, must corrosion-protected.2. suitable coating
must applied corrosion protection connection
points the ground.7.1 Materials for air-termination and conductor
systems
The following materials are preferred for use extern-
al lightning protection systems: Hot galvanised steel,
rustproof steel, copper and aluminium.
Variable bi-metal quick connector with bi-metal intermedi-
ate plate (copper/aluminium)
TBS
Blitzschutz-Leitfaden
2018
/
en
/
2020/01/10
14:42:40
14:42:40
(LLExport_02613)
/
2020/01/10
14:42:54
14:42:54
170
Chapter The external lightning protection system
.
Corrosion
A risk corrosion occurs especially when joining dif-
ferent material types. For this reason, copper parts
may installed above galvanised surfaces above
aluminium parts copper particles worn away by
rain other environmental influences can penetrate
the galvanised surface