Lightning protection guide by OBO

| Kategorie: Katalog  |

Last revision 2020

Vydal: OBO BETTERMANN s. r. o. Autor: OBO BETTERMANN

Strana 61 z 288

Jak získat tento dokument?






Poznámky redaktora
Air-termina- tion systems are required the dark grey areas. Only the planning methods named IEC/EN 62305-3 shall be used for planning. The air-termination rods must arranged such way that all parts the structure protected are located the protection area the air-termination system. For all types air-termination system, only the actual dimensions the metallic air-termination system shall be taken into account during planning according to IEC/EN 62305-3. Others, such the "Collection Volume Method" (CVM), are excluded the stand- ard. The rolling sphere method can used determine the required lengths air-termination rods and the distances between them. Air-termination rod Rolling sphere radius Protection area air-termination rod determined us- ing the rolling sphere method TBS Blitzschutz-Leitfaden 2018 / en / 2020/01/10 14:42:40 14:42:40 (LLExport_02613) / 2020/01/10 14:42:54 14:42:54 61 Chapter The external lightning protection system .TBS Blitzschutz-Leitfaden 2018 / en / 2020/01/10 14:42:40 14:42:40 (LLExport_02613) / 2020/01/10 14:42:54 14:42:54 Rolling sphere method (dark grey areas are areas risk strike) The building that protected must fitted with air-termination systems such way that sphere with radius determined the basis the lightning protection class cannot touch the building. This should also taken into ac- count with all so-called "active" air-termination sys- tems, such ESE "Early Streamer Emission"