Lightning protection guide by OBO

| Kategorie: Katalog  |

Last revision 2020

Vydal: OBO BETTERMANN s. r. o. Autor: OBO BETTERMANN

Strana 146 z 288

Jak získat tento dokument?






Poznámky redaktora
Spark gap mounted insulating sections Ex spark gaps ISG H According TRGS 507, electrical separating ele- ments potentially explosive areas must bridged with spark gaps. The ATEX-certified OBO ISG spark gap insulates the parts the system against corrosion currents, ful- filling the requirements for the connection lightning currents potentially explosive areas according to IEC/EN 62561-3. The spark gaps must have re- sponse surge voltage 50% the testing voltage of the insulating elements, although with maximum of 2. Spark gap ISG H The OBO ISG spark gap certified according to the following directives for Zone 1/21 and 2/22: • ATEX • IECEx TBS Blitzschutz-Leitfaden 2018 / en / 2020/01/10 14:42:40 14:42:40 (LLExport_02613) / 2020/01/10 14:42:54 14:42:54 146 Chapter The external lightning protection system .5 kV. To avoid arcing insulating pieces areas, the use Ex-certified spark gaps required