Chapter Testing, maintenance and documentation
.
Alternatively, OBO Bettermann can include the
readout the data additional service. The
magnetic card reader offers the possibility evaluat-
ing the peak current sensors. The corresponding peak
current value shown the display.2: Test classes connecting components
PCS sensor down-conductor
Testing lightning protection systems with the
PCS system
The Peak Current Sensor (PCS) records and stores
pulsed currents the form magnetic card. This is
a method monitoring whether lightning has hit the
lighting current system and which maximum lightning
current has occurred. The results can
provide information potential damage the elec-
trical installation.TBS
Blitzschutz-Leitfaden
2018
/
en
/
2020/01/10
14:42:40
14:42:40
(LLExport_02613)
/
2020/01/10
14:42:54
14:42:54
Test class Tested with Application
H according IEC 62561-1
3 limp
100 (10/350)
Air-termination system
N according IEC 62561-1
3 limp
50 (10/350) Multiple applications along which the lightning current
can spread, least two arrestors
Table 4.
The PCS card mounted snapping card holder
onto the round conductor defined distance