The PCS card mounted snapping card holder onto the round conductor defined distance. the PCS system mounted between the interface from equipotential bonding to earthing system, the coupled lightning current a building can also measured.TBS Blitzschutz-Leitfaden 2018 / en / 2020/01/10 14:42:40 14:42:40 (LLExport_02613) / 2020/01/10 14:42:54 14:42:54 Test class Tested with Application H according IEC 62561-1 3 limp 100 (10/350) Air-termination system N according IEC 62561-1 3 limp 50 (10/350) Multiple applications along which the lightning current can spread, least two arrestors Table 4. TBS Blitzschutz-Leitfaden 2018 / en / 2020/01/10 14:42:40 14:42:40 (LLExport_02613) / 2020/01/10 14:42:54 14:42:54 275 Chapter Testing, maintenance and documentation . The results can provide information potential damage the elec- trical installation. The measuring range the card from 120 kA.2: Test classes connecting components PCS sensor down-conductor Testing lightning protection systems with the PCS system The Peak Current Sensor (PCS) records and stores pulsed currents the form magnetic card. This is a method monitoring whether lightning has hit the lighting current system and which maximum lightning current has occurred. this is desired, please contact your OBO representative or the appropriate subsidiary. The corresponding peak current value shown the display. The magnetic card reader offers the possibility evaluat- ing the peak current sensors. Alternatively, OBO Bettermann can include the readout the data additional service