Lightning protection guide by OBO

| Kategorie: Katalog  |

Last revision 2020

Vydal: OBO BETTERMANN s. r. o. Autor: OBO BETTERMANN

Strana 275 z 288

Jak získat tento dokument?






Poznámky redaktora
the PCS system mounted between the interface from equipotential bonding to earthing system, the coupled lightning current a building can also measured. The measuring range the card from 120 kA. this is desired, please contact your OBO representative or the appropriate subsidiary. TBS Blitzschutz-Leitfaden 2018 / en / 2020/01/10 14:42:40 14:42:40 (LLExport_02613) / 2020/01/10 14:42:54 14:42:54 275 Chapter Testing, maintenance and documentation . Alternatively, OBO Bettermann can include the readout the data additional service. The magnetic card reader offers the possibility evaluat- ing the peak current sensors. The corresponding peak current value shown the display.2: Test classes connecting components PCS sensor down-conductor Testing lightning protection systems with the PCS system The Peak Current Sensor (PCS) records and stores pulsed currents the form magnetic card. This is a method monitoring whether lightning has hit the lighting current system and which maximum lightning current has occurred. The results can provide information potential damage the elec- trical installation.TBS Blitzschutz-Leitfaden 2018 / en / 2020/01/10 14:42:40 14:42:40 (LLExport_02613) / 2020/01/10 14:42:54 14:42:54 Test class Tested with Application H according IEC 62561-1 3 limp 100 (10/350) Air-termination system N according IEC 62561-1 3 limp 50 (10/350) Multiple applications along which the lightning current can spread, least two arrestors Table 4. The PCS card mounted snapping card holder onto the round conductor defined distance