Lightning protection guide by OBO

| Kategorie: Katalog  |

Last revision 2020

Vydal: OBO BETTERMANN s. r. o. Autor: OBO BETTERMANN

Strana 199 z 288

Jak získat tento dokument?






Poznámky redaktora
Main earthing rail System fuse Back-up fuse Back-up fuse surge protection device Small fuses can destroyed by energy-rich surge currents. an upstream fuse (F1) has smaller equal value than the maximum fuse current, separate fuse/back-up fuse (F2) however not needed before the surge pro- tection device. the rating the system fuse (F1) is higher than the maximum fuse current, fuse corres- ponding the specified maximum fuse current must be fitted before the protection device. OBO specifies maximum fuse rating for all devices. The pulse resistance higher- rated fuse greater than that lower-rated one. The rating the fuse (F2) before the protection device should as high possible. TBS Blitzschutz-Leitfaden 2018 / en / 2020/01/10 14:42:40 14:42:40 (LLExport_02613) / 2020/01/10 14:42:54 14:42:54 199 Chapter The internal lightning protection system .TBS Blitzschutz-Leitfaden 2018 / en / 2020/01/10 14:42:40 14:42:40 (LLExport_02613) / 2020/01/10 14:42:54 14:42:54 Back-up fuse To provide protection case short circuits surge protection devices, back-up fuse (F2) used