Poznámky redaktora
Because the foundation earther longer has contact with the earth here, additional grid ring earther must created. To ensure contact with the earth, water-impermeable concrete must not used.4 Perimeter insulation Perimeter insulation heat insulation, which sur- rounds the area the structure contact with the earth from outside. The founda- tion earther can implemented the concrete. If the exterior walls and the foundation plate are sur- rounded with perimeter insulation, the earther the floor plate still has some earthing effect the strip foundation open the bottom. If the building structure surrounded all sides by perimeter insulation, i. If the perimeter insulation only the surrounding walls, earther contact often still intact.e. all surrounding walls, strip foundations and the bottom the foundation, the function the foundation earther longer fulfilled. TBS Blitzschutz-Leitfaden 2018 / en / 2020/01/10 14:42:40 14:42:40 (LLExport_02613) / 2020/01/10 14:42:54 14:42:54 162 Chapter The external lightning protection system .Insulated floor plate (perimeter insulation, shown here blue) 2. Connection lugs must routed into the building such way that they are resistant pressurised water above the maximum groundwater level. often consists polyurethane foam sheets crushed glass.4.4. functional equipotential bonding cable must created the foundation