2 Down-conductors Down-conductors are the part the external lightning protection system designed route the lightning cur- rent from the air-termination system the earthing system. The number conductors derived from the scope of the building protected, although least two conductors are required every case. TBS Blitzschutz-Leitfaden 2018 / en / 2020/01/10 14:42:40 14:42:40 (LLExport_02613) / 2020/01/10 14:42:54 14:42:54 96 Chapter The external lightning protection system . Care must taken ensure that the current paths are short and installed without loops. The conductor system routes the lightning current from air-termination system earthing system. Table 2.Down-conductor system according IEC 62305-3 2. order reduce the probability damage from the lightning current flowing through the lightning protection system, the down-conductors should at- tached such way that, between the impact point and the earth: • Multiple parallel current routes exist • The length the down-conductors kept short as possible • Equipotential bonding created between the con- ductive parts the building structure.22 shows the distances between the conductors and the corresponding lightning protection classes