Isolated lightning protection with correctly maintained separation distance (s) Application example Roof structures Situation Air-conditioning systems, photovoltaic systems, elec- trical sensors/actuators metallic vent pipes with conductive connection into the building. ki Dependent the selected protection class the lightning protection system kc Dependent the (partial) lightning current that flows into the conductors km Dependent the material the electrical insulation L(m) Vertical distance from the point at which the separation distance (s) calculated up the closest point the equipotential bonding Formula for calculating the separation distance TBS Blitzschutz-Leitfaden 2018 / en / 2020/01/10 14:42:40 14:42:40 (LLExport_02613) / 2020/01/10 14:42:54 14:42:54 74 Chapter The external lightning protection system . Solution Isolation through the use separation distance (s) Note Risk inductively coupled surges must con- sidered