Lightning protection guide by OBO

| Kategorie: Katalog  |

Last revision 2020

Vydal: OBO BETTERMANN s. r. o. Autor: OBO BETTERMANN

Strana 67 z 288

Jak získat tento dokument?






Poznámky redaktora
1. TBS Blitzschutz-Leitfaden 2018 / en / 2020/01/10 14:42:40 14:42:40 (LLExport_02613) / 2020/01/10 14:42:54 14:42:54 67 Chapter The external lightning protection system . S shape), because they are flexible lines.5: Incorporation roof structures Smoke and heat extraction roof light domes must protected from direct lightning strikes. Surge protection devices protect the electrical drives these devices from damage due inductive coupling. Material Expansion piece spacing m Steel 15 Stainless steel 10 Copper 10 Aluminium 10 Table 2. For practic- al purposes, the expansion piece spacings listed in Table 2. summer, the length of the air-termination systems and down-conductors changes.5.1.3 above roof level 1.2 Changes length due temperature At higher temperatures, e.g.3 External lightning protection for roof struc- tures Roof structures must incorporated into the external lightning protection system according IEC 62305-3 if they exceed the dimensions stated Table 2. Roof structures Dimensions Metal 0.TBS Blitzschutz-Leitfaden 2018 / en / 2020/01/10 14:42:40 14:42:40 (LLExport_02613) / 2020/01/10 14:42:54 14:42:54 2.5 above the air-termination system Table 2.g.4: Expansion pieces compensate changes in length due temperature 2. These temperature-related changes length must taken into account during installation. Ex- pansion pieces must allow flexible response to changes length, either through their shape (e.4 have proved effective.0 length the structure Non-metal 0.0 total area 2