Lightning protection guide by OBO

| Kategorie: Katalog  |

Last revision 2020

Vydal: OBO BETTERMANN s. r. o. Autor: OBO BETTERMANN

Strana 67 z 288

Jak získat tento dokument?






Poznámky redaktora
5 above the air-termination system Table 2. summer, the length of the air-termination systems and down-conductors changes.4 have proved effective. TBS Blitzschutz-Leitfaden 2018 / en / 2020/01/10 14:42:40 14:42:40 (LLExport_02613) / 2020/01/10 14:42:54 14:42:54 67 Chapter The external lightning protection system .4: Expansion pieces compensate changes in length due temperature 2.TBS Blitzschutz-Leitfaden 2018 / en / 2020/01/10 14:42:40 14:42:40 (LLExport_02613) / 2020/01/10 14:42:54 14:42:54 2.1. These temperature-related changes length must taken into account during installation.5: Incorporation roof structures Smoke and heat extraction roof light domes must protected from direct lightning strikes.1.2 Changes length due temperature At higher temperatures, e. Surge protection devices protect the electrical drives these devices from damage due inductive coupling.g. Material Expansion piece spacing m Steel 15 Stainless steel 10 Copper 10 Aluminium 10 Table 2. Ex- pansion pieces must allow flexible response to changes length, either through their shape (e. S shape), because they are flexible lines.0 length the structure Non-metal 0.3 above roof level 1.3 External lightning protection for roof struc- tures Roof structures must incorporated into the external lightning protection system according IEC 62305-3 if they exceed the dimensions stated Table 2.5.0 total area 2. Roof structures Dimensions Metal 0. For practic- al purposes, the expansion piece spacings listed in Table 2.g