Lightning protection guide by OBO

| Kategorie: Katalog  |

Last revision 2020

Vydal: OBO BETTERMANN s. r. o. Autor: OBO BETTERMANN

Strana 67 z 288

Jak získat tento dokument?






Poznámky redaktora
5 above the air-termination system Table 2.g.4: Expansion pieces compensate changes in length due temperature 2. For practic- al purposes, the expansion piece spacings listed in Table 2. summer, the length of the air-termination systems and down-conductors changes.4 have proved effective. Surge protection devices protect the electrical drives these devices from damage due inductive coupling.0 total area 2. S shape), because they are flexible lines.3 above roof level 1. Ex- pansion pieces must allow flexible response to changes length, either through their shape (e.1.g.3 External lightning protection for roof struc- tures Roof structures must incorporated into the external lightning protection system according IEC 62305-3 if they exceed the dimensions stated Table 2.5: Incorporation roof structures Smoke and heat extraction roof light domes must protected from direct lightning strikes. TBS Blitzschutz-Leitfaden 2018 / en / 2020/01/10 14:42:40 14:42:40 (LLExport_02613) / 2020/01/10 14:42:54 14:42:54 67 Chapter The external lightning protection system .5.0 length the structure Non-metal 0. Material Expansion piece spacing m Steel 15 Stainless steel 10 Copper 10 Aluminium 10 Table 2.1. Roof structures Dimensions Metal 0. These temperature-related changes length must taken into account during installation.2 Changes length due temperature At higher temperatures, e.TBS Blitzschutz-Leitfaden 2018 / en / 2020/01/10 14:42:40 14:42:40 (LLExport_02613) / 2020/01/10 14:42:54 14:42:54 2