This method should therefore only used where the building already protected with air-termination rods whose positions were determined using the rolling sphere grid method.TBS Blitzschutz-Leitfaden 2018 / en / 2020/01/10 14:42:40 14:42:40 (LLExport_02613) / 2020/01/10 14:42:54 14:42:54 Protective angle Separation distance Protective angle and separation distance air-termination rods photovoltaic system 2. Using the protective angle method is only advisable simple small buildings and for parts build- ings. The protective angle method is well suited determining the positions air-termin- ation rods providing merely additional protection for a small number protruding building parts struc- tures. All roof structures must protected with air-termina- tion rods.1. TBS Blitzschutz-Leitfaden 2018 / en / 2020/01/10 14:42:40 14:42:40 (LLExport_02613) / 2020/01/10 14:42:54 14:42:54 63 Chapter The external lightning protection system .g. with stainless steel pipe with a connection the ventilation air-conditioning sys- tem), then the air-termination rod must erected a separation distance (s) from the object pro- tected.1. If the roof structure has conductive continuation into the building (e. Here necessary observe the relevant separation distance (“s”) between earthed roof struc- tures and metal systems. This distance safely prevents arcing the lightning current and dangerous spark creation.2 Protective angle method Using the protective angle method only advisable in simple small buildings and for individual sections of buildings