Lightning protection guide by OBO

| Kategorie: Katalog  |

Last revision 2020

Vydal: OBO BETTERMANN s. r. o. Autor: OBO BETTERMANN

Strana 63 z 288

Jak získat tento dokument?






Poznámky redaktora
TBS Blitzschutz-Leitfaden 2018 / en / 2020/01/10 14:42:40 14:42:40 (LLExport_02613) / 2020/01/10 14:42:54 14:42:54 Protective angle Separation distance Protective angle and separation distance air-termination rods photovoltaic system 2.1. Using the protective angle method is only advisable simple small buildings and for parts build- ings. The protective angle method is well suited determining the positions air-termin- ation rods providing merely additional protection for a small number protruding building parts struc- tures. with stainless steel pipe with a connection the ventilation air-conditioning sys- tem), then the air-termination rod must erected a separation distance (s) from the object pro- tected. TBS Blitzschutz-Leitfaden 2018 / en / 2020/01/10 14:42:40 14:42:40 (LLExport_02613) / 2020/01/10 14:42:54 14:42:54 63 Chapter The external lightning protection system .g. Here necessary observe the relevant separation distance (“s”) between earthed roof struc- tures and metal systems. All roof structures must protected with air-termina- tion rods. If the roof structure has conductive continuation into the building (e. This method should therefore only used where the building already protected with air-termination rods whose positions were determined using the rolling sphere grid method.2 Protective angle method Using the protective angle method only advisable in simple small buildings and for individual sections of buildings.1. This distance safely prevents arcing the lightning current and dangerous spark creation