Lightning protection guide by OBO

| Kategorie: Katalog  |

Last revision 2020

Vydal: OBO BETTERMANN s. r. o. Autor: OBO BETTERMANN

Strana 63 z 288

Jak získat tento dokument?






Poznámky redaktora
If the roof structure has conductive continuation into the building (e. Here necessary observe the relevant separation distance (“s”) between earthed roof struc- tures and metal systems. The protective angle method is well suited determining the positions air-termin- ation rods providing merely additional protection for a small number protruding building parts struc- tures. This method should therefore only used where the building already protected with air-termination rods whose positions were determined using the rolling sphere grid method. with stainless steel pipe with a connection the ventilation air-conditioning sys- tem), then the air-termination rod must erected a separation distance (s) from the object pro- tected. This distance safely prevents arcing the lightning current and dangerous spark creation.TBS Blitzschutz-Leitfaden 2018 / en / 2020/01/10 14:42:40 14:42:40 (LLExport_02613) / 2020/01/10 14:42:54 14:42:54 Protective angle Separation distance Protective angle and separation distance air-termination rods photovoltaic system 2. All roof structures must protected with air-termina- tion rods.1.1.g. Using the protective angle method is only advisable simple small buildings and for parts build- ings. TBS Blitzschutz-Leitfaden 2018 / en / 2020/01/10 14:42:40 14:42:40 (LLExport_02613) / 2020/01/10 14:42:54 14:42:54 63 Chapter The external lightning protection system .2 Protective angle method Using the protective angle method only advisable in simple small buildings and for individual sections of buildings