However, decisive importance for the protection ac-
tion that the protection level the surge protection
device below the surge voltage resistance the
lights and the LED driver.
Surge protection devices must
correspond IEC 61643.
(Source: Luminaires 60598-1)
Installation location Description Protection device Item no.Installation location the lightning and surge
protection
The use surge protection required for safe opera-
tion.
Lamp head with LED system, before the LED driver Surge protection type ÜSM-20-230L1+PE 5092431
Connection compartment the mast luminaire
Surge protection module,
type 2+3
ÜSM-20-230I1P+PE 5092431
Control cabinet with electronics, supply Surge protection type 1+2 V50 combination arrestor 5093526
Earthing line, uninsulated Flat round conductor 5018730
Supply cable
Direct lightning strike into the mast luminaire
TBS
Blitzschutz-Leitfaden
2018
/
en
/
2020/01/10
14:42:40
14:42:40
(LLExport_02613)
/
2020/01/10
14:42:54
14:42:54
212
Chapter The internal lightning protection system
.
According the testing standard, each protection
device must have thermal monitoring and must be
isolated safely there defect. According the American ANSI and IEEE stand-
ard, surge voltage resistance required
for outdoor lighting surge current load kA."
If there direct lightning strike the mast lumin-
aire, large portion the lightning current will flow
directly into the earth, creating potential difference to
the supply cable.32 specifies: "Surge protection devices must
meet IEC 61643. Surge protection devices
must correspond the testing standard IEC 61643-
11 and must able arrest surge currents sever-
al thousand amps multiple times without destruction.
The luminaire standard "Fpr 60598-1: 2012-11 Lu-
minaires Part General Requirements and Tests",
Point 4. Powerful lightning current combin-
ation arrestors can arrest the energy-rich currents