Lightning protection guide by OBO

| Kategorie: Katalog  |

Last revision 2020

Vydal: OBO BETTERMANN s. r. o. Autor: OBO BETTERMANN

Strana 203 z 288

Jak získat tento dokument?






Poznámky redaktora
73 Table 3. sheet 5).TBS Blitzschutz-Leitfaden 2018 / en / 2020/01/10 14:42:40 14:42:40 (LLExport_02613) / 2020/01/10 14:42:54 14:42:54 Avoiding shade from the lightning protection sys- tem The position the air-termination masts air-termina- tion rods should chosen that there shad- ing the modules.008 0. air-termin- ation rod must least 108 diameter from the PV module (DIN 62305-3 Suppl.86 0. Diameter the air-termina- tion system (m) Distance between the air- termination system and the PV module (m) 0.010 1.6: Minimum distance from the air-termination sys- tems, avoid core shadow An air termination rod casting shadow module Solar radiation Air-termination rod PV system TBS Blitzschutz-Leitfaden 2018 / en / 2020/01/10 14:42:40 14:42:40 (LLExport_02613) / 2020/01/10 14:42:54 14:42:54 203 Chapter The internal lightning protection system .016 1. core shadow can cause per- formance reductions the whole string.08 0. Note that the system must remain the protection area the air-termination rod