Lightning protection guide by OBO

| Kategorie: Katalog  |

Last revision 2020

Vydal: OBO BETTERMANN s. r. o. Autor: OBO BETTERMANN

Strana 179 z 288

Jak získat tento dokument?






Poznámky redaktora
1.1 Minimum dimensions cables Minimum cross-sections according IEC 62305-3 for lightning protection equipotential bonding Material Cross-section cables connecting different equipotential busbars with one another or with the earthing system Copper mm² Aluminium mm² Steel mm² Table 3. To implement equipotential bonding correctly, there- fore necessary select the right components use. 3.2: Minimum dimensions cables, protection class IV TBS Blitzschutz-Leitfaden 2018 / en / 2020/01/10 14:42:40 14:42:40 (LLExport_02613) / 2020/01/10 14:42:54 14:42:54 179 Chapter The internal lightning protection system .TBS Blitzschutz-Leitfaden 2018 / en / 2020/01/10 14:42:40 14:42:40 (LLExport_02613) / 2020/01/10 14:42:54 14:42:54 Equipotential bonding according IEC 60364-4- 41 and IEC 60364-5-54 Protective conductors must protected suitable manner against mechanical damage, chemical or electrochemical destruction well against electro- dynamic and thermodynamic forces. Equipotential busbars and earthing clamps are key components this kind installation. the context of lightning protection equipotential bonding, these must fulfil the requirements and undergo tests as defined IEC 62561-1. Connections for testing purposes are permit- ted. Material Cross-section cables connecting the in- ternal metallic installations with the equi- potential busbar Copper mm² Aluminium mm² Steel mm² Table 3. Switching devices must not inserted into the protective con- ductor.2 Versions Each system has different environmental and normat- ive requirements relating equipotential bonding