3.
Material
Cross-section cables connecting the in-
ternal metallic installations with the equi-
potential busbar
Copper mm²
Aluminium mm²
Steel mm²
Table 3.2 Versions
Each system has different environmental and normat-
ive requirements relating equipotential bonding.TBS
Blitzschutz-Leitfaden
2018
/
en
/
2020/01/10
14:42:40
14:42:40
(LLExport_02613)
/
2020/01/10
14:42:54
14:42:54
Equipotential bonding according IEC 60364-4- 41
and IEC 60364-5-54
Protective conductors must protected suitable
manner against mechanical damage, chemical or
electrochemical destruction well against electro-
dynamic and thermodynamic forces.1.1 Minimum dimensions cables
Minimum cross-sections according IEC 62305-3
for lightning protection equipotential bonding
Material
Cross-section cables connecting different
equipotential busbars with one another or
with the earthing system
Copper mm²
Aluminium mm²
Steel mm²
Table 3. Switching
devices must not inserted into the protective con-
ductor.
Equipotential busbars and earthing clamps are key
components this kind installation.2: Minimum dimensions cables, protection
class IV
TBS
Blitzschutz-Leitfaden
2018
/
en
/
2020/01/10
14:42:40
14:42:40
(LLExport_02613)
/
2020/01/10
14:42:54
14:42:54
179
Chapter The internal lightning protection system
. To
implement equipotential bonding correctly, there-
fore necessary select the right components use. the context
of lightning protection equipotential bonding, these
must fulfil the requirements and undergo tests as
defined IEC 62561-1. Connections for testing purposes are permit-
ted