Lightning protection guide by OBO

| Kategorie: Katalog  |

Last revision 2020

Vydal: OBO BETTERMANN s. r. o. Autor: OBO BETTERMANN

Strana 168 z 288

Jak získat tento dokument?






Poznámky redaktora
with pulse voltage min.1 Step voltage The step voltage the voltage between person’s feet placed apart.2 Protection against dangerous touch voltage The isCon® conductor Pro+ can used as protection against dangerous touch voltage. the conductor) and earth potential. 100 kV (1.g. Here the current flows from the hand the foot through the body.6. This is particularly required areas with groups people.2. U B1 U B2 U E U S FE FE SE + 1m UE : Earthing voltage UB1 : Touch voltage without potential control (on founda- tion earth electrode) UB2 : Touch voltage with potential control (foundation earth electrode and control earther) Us : Step voltage (without control earther) φ: Earth surface potential FE: Foundation earth electrode SE: Control earth electrode (ring earth electrode) Electrical potential the earth surface and voltages current passes through the foundation earth electrode (FE) and control earther (SE) TBS Blitzschutz-Leitfaden 2018 / en / 2020/01/10 14:42:40 14:42:40 (LLExport_02613) / 2020/01/10 14:42:54 14:42:54 168 Chapter The external lightning protection system .6. 2. The isCon® conductor Pro+ was tested a length max. The contact voltage the voltage between component (e. Here the current flows between the person's feet through their body. Both types voltage can harm- ful the body.2/50 μs) rain and fulfils the requirements for touch protection according IEC/EN 62305-3. These voltages need reduced via potential control insulation