Lightning protection guide by OBO

| Kategorie: Katalog  |

Last revision 2020

Vydal: OBO BETTERMANN s. r. o. Autor: OBO BETTERMANN

Strana 135 z 288

Jak získat tento dokument?






Poznámky redaktora
Beginning with the secured operating field strengths for the long-time range, the following image shows extrapolation the field strength for the short-time range few 100 ns. During the expected lifespan lightning protection system, insulated, high-voltage-resistant conductor must withstand multiple lightning events. For this reason, the insulating material can used up to close the limit the theoretical resistance of 250 kV/mm [Ushakov]. doing, the cross-section the copper conductor selected such way that sufficient lightning current carrying capacity and acceptable flexibility for routing are given, but, the same time, the standard specifications from IEC/EN 62305-3 are fulfilled.2. However, this assumes the use high-quality materials for the internal and ex- ternal conductive layer, the insulating material and for the resistive field control. The properties the materi- als are checked high-voltage test.5 Technical solution for insulated high- voltage-resistant conductor The insulation material not constantly subject to voltage, meaning that aging processes not play a role medium and high-voltage cables the power supply. Electrical field strength kV/mm Load period s Sample from type guide Theoretical limit according Ushakov Ed extrapolated Ed secured experimentally, Hz TBS Blitzschutz-Leitfaden 2018 / en / 2020/01/10 14:42:40 14:42:40 (LLExport_02613) / 2020/01/10 14:42:54 14:42:54 135 Chapter The external lightning protection system .TBS Blitzschutz-Leitfaden 2018 / en / 2020/01/10 14:42:40 14:42:40 (LLExport_02613) / 2020/01/10 14:42:54 14:42:54 2. From the type tests carried out, the field strengths effective the test can calculated and are shown points the image.13. They match the theoretical field strength. The extrapolation covers the theoretical field strength given Ushakov for the short-time range 250 kV/mm for the time range 100 ns. Overview the electrical field strength for insulation ma- terials high-voltage cables and extrapolated values for the short-time range, well two protected values from type tests insulated conductors. The below image shows finished and patented design insulated, high-voltage-resistant con- ductor