26: Minimum required distance between connec- tion element and potential connection terminal = 0.75 air isFang air-termination rods with external isCon® conduct- or TBS Blitzschutz-Leitfaden 2018 / en / 2020/01/10 14:42:40 14:42:40 (LLExport_02613) / 2020/01/10 14:42:54 14:42:54 126 Chapter The external lightning protection system .Example: isCon® conductor isolated ring circuit Connection element Potential connection x: Minimum distance (smaller values are possible based calculation) y: Distance from GRP holder wall h: Distance from wall mounting flat roof Equipotential bonding mm² Clip distance (x) from the potential connection terminal to the connection element cm Calculated separation distance (s) cm isCon SW isCon Pro+ SW/GR and isCon Pro SW isCon SW Table 2