Operating Instructions for the Petersen-Coil Regulator

Vydal: EBERLE Controls GmbH

Strana 82 z 272

Jak získat tento dokument?






Poznámky redaktora
Figure 66: Downloading parameters from REG-DP/ REG-DPA after successful linearization 10. Once linearization has been completed, advisable download the determined param- eters from the regulator and back them up.Page Commissioning We take care it. .4 Factory settings for certain parameters If you are only going use the regulator's standard functions classic regulation P-coil –, the following default settings can adopted: The binary inputs and outputs are predefined upon delivery, but the settings can be changed for all inputs and outputs. Figure 64: Press (COPY R[%]) accept the current position  Correcting the current value the P-coil value that was set site Figure 65: Adjust the coil position the Ipos column  Repeat the last four steps until all the eight values have been set Imax has been reached.  Remember press <ENTER> confirm the determined linearization table