40 Une_?? Message Error detected the measurement the zero sequence
voltage, Une 120% the set nominal voltage., cable break).
46 Usync<< Reference voltage smaller than VAC Angle cannot be
measured.
42 E:ERROR Message: Forwarding the input message 'E-Error'. Switching absolute value evaluation.
50 Local The regulator operating mode 'Local'. The residual current increased when
the next earth fault occurs.
48 SearchDelay set when the regulator search delay, meaning that the zero
sequence voltage outside the tolerance range and the regula-
tor has not yet started searching.g..
43 CouplSignal Message: Bus bars are coupled
44 CouplViaNet Only when using current injection
Message: Grid coupled Testing done with current injection
The feature and 'check external coupling' parameter must be
enabled the Parallel regulation menu
45 E-LAN Error Message: Summary message for E-LAN errors.
41 E:MAN Message: Forwarding the input message 'E-Man'.
37 n_Search Message: The P-coil could not successfully tuned after
'Searchcycle_max'. also set during the forced
search delay:
49 ParaProg set when parallel regulation enabled and activated the
clutch switch.
39 PotiError Message: Error detected the measurement the coil position,
(e.
.
0 SearchTime exceeded (BOF 38:T_MotOn)
0 NumberSearch exceeded (BOF 37: search)
Error
0 Motor error
– movement adjustment command (BOF
33:E:Move)
– Wrong direction (BOF 32:E:Dir)
0 Potentiometer error
– Cable break (BOF 39:Pot_???)
0 Both end switches are recognized the same time
0 Positioning error
0 P-coil error message (BIF 10:E:Error )
Status:
0 All internal errors such as
– RAM
– E-LAN
– Battery
– .
51 Remote The regulator operating mode 'Remote'.
47 R_armed Resistor control primed.
38 >T_MotOn Message: The set 'Motor runtime max' was exceeded..Page 140 Detailed description REG-DP/ REG-DPA parameters