37 n_Search Message: The P-coil could not successfully tuned after
'Searchcycle_max'..
43 CouplSignal Message: Bus bars are coupled
44 CouplViaNet Only when using current injection
Message: Grid coupled Testing done with current injection
The feature and 'check external coupling' parameter must be
enabled the Parallel regulation menu
45 E-LAN Error Message: Summary message for E-LAN errors.
0 SearchTime exceeded (BOF 38:T_MotOn)
0 NumberSearch exceeded (BOF 37: search)
Error
0 Motor error
– movement adjustment command (BOF
33:E:Move)
– Wrong direction (BOF 32:E:Dir)
0 Potentiometer error
– Cable break (BOF 39:Pot_???)
0 Both end switches are recognized the same time
0 Positioning error
0 P-coil error message (BIF 10:E:Error )
Status:
0 All internal errors such as
– RAM
– E-LAN
– Battery
– .
50 Local The regulator operating mode 'Local'.
47 R_armed Resistor control primed.
38 >T_MotOn Message: The set 'Motor runtime max' was exceeded. also set during the forced
search delay:
49 ParaProg set when parallel regulation enabled and activated the
clutch switch.
41 E:MAN Message: Forwarding the input message 'E-Man'.g.
.
40 Une_?? Message Error detected the measurement the zero sequence
voltage, Une 120% the set nominal voltage.Page 140 Detailed description REG-DP/ REG-DPA parameters
We take care it. Switching absolute value evaluation.
42 E:ERROR Message: Forwarding the input message 'E-Error'.
51 Remote The regulator operating mode 'Remote'.
46 Usync<< Reference voltage smaller than VAC Angle cannot be
measured. The residual current increased when
the next earth fault occurs.
39 PotiError Message: Error detected the measurement the coil position,
(e., cable break)..
48 SearchDelay set when the regulator search delay, meaning that the zero
sequence voltage outside the tolerance range and the regula-
tor has not yet started searching