57 dIce_max_nc set when the regulator the self-extinguishing current limit
dIce the state 'Tuned_nc'. The target detun-
ing exceeded.
The battery should replaced within the next months!
59 CI_extern Only when used EDC-Sys/EOR-DM
Message: Current injection requested from external device here
by earth fault detection (EOR-DM)
60 CI_alive Message: Communication for current injection available
61 CI_on Message: Current injection active.
56 dIce_max set when the self-extinguishing current limit dIce exceeded.
62 CI_blocked Message: Current injection blocked:
0 Signal forwarded from defined binary input
0 Signalling from current injection controller
63 CI_failure Message:
0 Communication error CIC
0 Error message, error CIC
0 Missing synchronization voltage CIC
0 Connection interruption detected between CIC and P-coil
0 Short circuit connection between CIC and P-coil
64 CI_missing Message: response from CIC
65 Fix_on Command: Request from REG-DP/ REG-DPA activate the fixed
coil
66 Pulse:Fix_on Impulse command: Request from REG-DP/ REG-DPA activate
the fixed coil
67 Pulse:Fix_off Impulse command: Request from REG-DP/ REG-DPA deactivate
the fixed coil
68 Rs2_on Only for 'ENEL' feature
69 Rs12_on Only for 'ENEL' feature
70 Rp_on Only for 'ENEL' feature
71 Pulse:Rp_on Only for 'ENEL' feature
72 Pulse:Rp_off Only for 'ENEL' feature
73 R_nCB_Trip Only for 'CBR' feature
74 UserBOF1 User-defined binary output functions (BOF)
All the output functions listed here can grouped one out-
. Current being injected.
53 Search Set during the search process:
From the start the search (Tuned Tnd.nc Tuned Umin
OR SearchCan)
The message reset by: Earth fault, Blocking, MAN, slave mode
54 Umax_End set when the Umax_end threshold exceeded.
58 Batt low Message: The charge level the REG-DP/ REG-DPA's buffer bat-
tery critical.
55 Umax_end_K set when tuning point found Umax_end.Page 141
Detailed description REG-DP/ REG-DPA parameters
52 Uerd Pos Earth fault AND positioning the P-coil are completed during the
earth fault