Petersenova cívka s regulátorem REG-DP

| Kategorie: Leták / Datasheet  |

Operating Instructions for the Petersen-Coil Regulator

Vydal: EBERLE Controls GmbH

Strana 240 z 272

Jak získat tento dokument?






Poznámky redaktora
The absolute value and especially the phase must the same both measurement inputs.: coil nominal voltage/100 V Knu 120 – current measurement inputs Current transformer HPCI module The current through the power auxiliary winding measured directly the HPCI with a 200/1 current transformer. Default value: 30° .  Setting for current input: Setting Description Ici Current injected PAW - wired cabinet default current channel 1 Default allocation current channels Measurement channel Default allocation and settings I1 Ici Ex. This transformer factor integrated the HPCI's firmware.Page 240 Commissioning the HPCI We take care it. However, the same zero sequence voltage measured both devices. Configuration voltage channel 2 Measurement channel Default allocation and settings U2 Uns_Coil Ex. Values increments 15° can entered. The conversion ratio knu for the value Uns_Coil then 120. Because the current injected the PAW, the ratio 12000 V/500 for the current transformer factor (kni) can set there. The current Ici already measured the sec- ondary side the current injection controller.: coil nominal voltage/500 power auxiliary winding (PAW) Kni 24 In the example, the coil's nominal voltage kV, the transformer's nominal value 100 V and the PAW's 500 V. The reason for this that the synchronization voltage Usync the REG-DP/ REG-DPA may not have the same phase the synchronization voltage the current injection controller. – Phase U-Sync (parameter hidden) The value determined during commissioning testing the polarity the current and voltage channels