Petersenova cívka s regulátorem REG-DP

| Kategorie: Leták / Datasheet  |

Operating Instructions for the Petersen-Coil Regulator

Vydal: EBERLE Controls GmbH

Strana 20 z 272

Jak získat tento dokument?






Poznámky redaktora
U3N U2N U1N C1 C3 LP Ip IC2 IC3 N U1E U2E U3E UNE earth IF ZF=0 I1 I2 I3 GP Figure The equivalent circuit resonant earthed neutral system with P-coil and a single phase-to-earth fault Une U31 1 2 3 U21 Ground IC2+ IC3 ILp IC2 IC3 IGp IP Uen IGp IF ILp IC2+IC3 under compensation over compensation full compensation a) b) Figure Vector diagram with earth fault phase (fault impedance Ω) b) Impact different tuning positions fault current IF LP, P-coil (inductance and conductance) C1, C2, Line-to-earth capacitances ZF Impedance the faulty section N Neutral point the transformer U1E, U2E, U3E Phase voltages UNE Zero sequence voltage IC2, IC3 Capacitive currents the two healthy lines IP Current through the P-coil when earth fault occurs IGP Active component IP ILP Reactive component IP IF Current across the faulty section The following assumptions are made for the derivatives: 0 The line-to-earth capacitances and conductances are symmetrical 0 All unbalances are allocated Line 1 0 For first observations, load current flowing .Page Applications We take care it