28 SIM Internal grid simulation has been activated.
23 R_auto_on Message: Resistance control has been activated. s). The
'Motor Higher' and 'Motor Lower', 'MAN' and 'AUTO' keys the
regulator are blocked the software.
25 R_on Command: Turn resistor for resistance control
26 R_T>> Message: Resistor too hot.
22 Coupling Message: Parallel operation P-coils; corresponds forwarding
input function '29: Coupling.
29 Alarm Alarm collective message:
0 SearchTime exceeded (BOF 38:T_MotOn)
0 NumberSearch exceeded (BOF 37: search)
0 responsive (BOF 64: CI_missing)
0 measured value too small
0 slave responsive (BOF 83: Slave missing)
30 Alarm Alarm collective message delayed
31 AlarmInt Reserved
32 E:Dir Message: P-coil moving the wrong direction
33 E:Move Message: P-coil adjustment 'Motor Higher' 'Motor Lower'
command was not detected within defined period (ca.
24 R_block Message: Resistance control active but blocked. The signals are not physical-
ly separated from the P-coil.
21 Fix coil Message: The fixed coil taken into account when calculating the
compensation. The menu and the different display
modes can still used.
27 PotiWarning Message: Pot measured value not plausible (pot has 'gap' at
this location).
34 Error Error message: Summary message for known errors:
0 Motor error
– movement adjustment command (33:E:Move)
– Wrong direction (32:E:Dir)
0 Potentiometer error
– Cable break (39:PotError)
0 Both end switches are recognized the same time
0 Positioning error
0 P-coil error message (BIF 10:E:Error )
35 Error_td Delayed summary error message
36 Error_Sum Error collective message
ErrSum
0 Error Alarm Status
0 (34:Error) (BOF 29:Alarm)
0 (BOF 4:EMERGStatus)
Alarm:
.Page 139
Detailed description REG-DP/ REG-DPA parameters
0 Search aborted
19 Homepos2 Reserved
20 Remote Message: The regulator was switched into 'Remote' mode