12 End_H/L Message: The regulator recognized the end position 'Higher' OR
'Lower'.
17 Block Message: The regulator operating mode AUTO but blocked by
an event.
14 Tuned Message tuned: The search process was completed successfully.Page 138 Detailed description REG-DP/ REG-DPA parameters
We take care it.
15 Tnd_nc Message tuned not compensated: The regulator took the precon-
ditions into account and adjusted the coil the best possible
value.
6 Une Uerd Message: The zero sequence voltage bigger than the set earth
fault threshold.
4 Status Message: Regulator status:
Summary message all self-test functions, such as
0 RAM/ROM
0 EEPROM
0 Battery empty
0 Watchdog
5 <AUTO> Message: The regulator operating mode AUTO.
16 Umax_nc Tuned not compensated message because the set Umax threshold
is preventing tuning.
1 PROG The relay allocated the background program.
2 Motor_H Command the P-coil: Adjust direction 'Higher'. The desired compensation value could not reached be-
cause outside the P-coil's adjustment range. The signal
is OR-gate for the position command 'Motor Higher', 'Motor
Lower' and the input 'Mot_Run'.
10 End_H Message: The regulator recognized the end position 'Higher'.
3 Motor_L Command the P-coil: Adjust direction 'Lower'. This message generated after the de-
fined delay time. It's put there by
EspRelPV.
7 Une Uerd_td Message delayed: The zero sequence voltage bigger than the set
earth fault threshold Uerd. Name Function
0 OFF: Relay not allocated.
Table 7-2: Set-up options for binary outputs and LEDs
No.
8 Une Umax Message: The zero sequence voltage bigger than the set maxi-
mum earth fault threshold Umax. This the OR-gate from the two previous messages.
18 Homepos1 Message: The regulator has reached the end position (standby
position last tuning position).
The desired compensation value was set successfully.
11 End_L Message: The regulator recognized the end position 'Lower'.
9 Une Umin Message: The regulator searched the whole adjustment range and
did not find zero sequence voltage bigger than the set minimum
zero sequence voltage. '0' '1' output based the inversion.
13 Mot_Run Message: The regulator recognized P-coil adjustment. This standby position moved
toward after:
0 Unsuccessful search because Uen Umin the whole adjust-
ment range