The below short list the recommended settings for classic regulation without addi-
tional current injection:
<F2>: Regulation
Regulation screen 1/2
<F2>: Default param
Default param Screen 1/4
F2: Search method
F3: Une tolerance:
F4: Delay search by:
F5: Delay forced search by:
Move coil
20.Page 83
Commissioning
The best way set the parameters that control the regulator's behaviour through
the control menu items (<MENU><F2><F2>) and set the desired parameters.0 s
5.0 s
Default param Screen 2/4
F2: Target tuning Type
F3: Target tuning
F4: Min adjustment dIpos/ %:
absolute[A]
+5 (absolute detuning recommended)
5.0
Default param Screen 4/4
F2: Max search cycles
F3: Motor runtime max/min
F4: End position when search cancelled:
F5: Standby position
10
45
tuning point (please select)
50.0%
10.0
<F4>: earth fault
Earth fault Screen 1/2
F2: Uerd threshold[%]
F3: Uerd message delay:
F4: Transient earth fault:
F5: Locking Uerd:
30.0 (should increased 180 s)
3.0 s
Off
Earth fault Screen 2/2
F2: Correction Ipos OFF:
.0
Default param Screen 3/4
F2: Exceed resonance peak:
F3: Readjust Uref/min:
F4: Une angle measurement
F5: Check resonance curve:
YES
5 min
On
1.0
7