Petersenova cívka s regulátorem REG-DP

| Kategorie: Leták / Datasheet  |

Operating Instructions for the Petersen-Coil Regulator

Vydal: EBERLE Controls GmbH

Strana 45 z 272

Jak získat tento dokument?






Poznámky redaktora
Ures Calculated zero sequence voltage Une the resonance point (Ipos Ires) Alternative for Ires, Iw, Ures: Ires Last measured calculated coil position which the maximum zero sequence voltage (Ures) was found d Grid damping specified activated fixed coil can taken into account (configurable) k Calculated grid unbalance . Ipos Current coil position that was measured and linearized using the potentiometer.4.g. When fixed coil activated, there option display it on the screen., the current that was ac- tually measured across the current transformer the P-coil A) Ires Last measured calculated coil position which the maximum zero sequence voltage (Ures) was found Iw Calculated active current component across the faulty section when a low impedance earth fault occurs.Page 45 Operating the REG-DP directly 9.2 <F3> Detailed view: The screen displays the following information: 0 Regulator status 0 Measured value for the zero sequence voltage Uen absolute value and angle 0 Current coil position Ipos 0 Calculated detuning v 0 Current measured across converter absolute value and angle 0 Calculated curve parameters Ires, and Ures Parameters Description Uen Current measured zero sequence voltage Une relation 100 as secondary voltage the voltage transformer primary voltage in kV. v Current detuning relation the resonance point that was measured or calculated during the last search process I1 Measured current for current transformer (e.1