Petersenova cívka s regulátorem REG-DP

| Kategorie: Leták / Datasheet  |

Operating Instructions for the Petersen-Coil Regulator

Vydal: EBERLE Controls GmbH

Strana 45 z 272

Jak získat tento dokument?






Poznámky redaktora
v Current detuning relation the resonance point that was measured or calculated during the last search process I1 Measured current for current transformer (e.4.1.Page 45 Operating the REG-DP directly 9. Ures Calculated zero sequence voltage Une the resonance point (Ipos Ires) Alternative for Ires, Iw, Ures: Ires Last measured calculated coil position which the maximum zero sequence voltage (Ures) was found d Grid damping specified activated fixed coil can taken into account (configurable) k Calculated grid unbalance . Ipos Current coil position that was measured and linearized using the potentiometer., the current that was ac- tually measured across the current transformer the P-coil A) Ires Last measured calculated coil position which the maximum zero sequence voltage (Ures) was found Iw Calculated active current component across the faulty section when a low impedance earth fault occurs.2 <F3> Detailed view: The screen displays the following information: 0 Regulator status 0 Measured value for the zero sequence voltage Uen absolute value and angle 0 Current coil position Ipos 0 Calculated detuning v 0 Current measured across converter absolute value and angle 0 Calculated curve parameters Ires, and Ures Parameters Description Uen Current measured zero sequence voltage Une relation 100 as secondary voltage the voltage transformer primary voltage in kV. When fixed coil activated, there option display it on the screen.g