0 Enter 100% for the power and press the 'Accept' key.
The calculated resonance curve
and the value for Ires are displayed the REG-DP/ REG-DPA.
14.
During the adjustment, the calculated value for Ires and should good constant.
.
Note:
If the regulation parameter still set 'Move coil', set back 'Current injection'.10 Testing the correct calculation across the P-coil's whole ad-
justment range
0 The REG_DP(A) must set MAN!
0 Select manual current injection the WinEDC service screen.9 Completing the commissioning current injection
After successful polarity test, the regulator can set AUTO mode and the resonance
curve calculated.Page 246 Commissioning the HPCI
We take care it.
14.
0 Current injection now continuous and new resonance curves are constantly calculat-
ed.
0 Move the coil manually (using the Higher and Lower keys the device) from the upper
to the lower end switch