Petersenova cívka s regulátorem REG-DP

| Kategorie: Leták / Datasheet  |

Operating Instructions for the Petersen-Coil Regulator

Vydal: EBERLE Controls GmbH

Strana 245 z 272

Jak získat tento dokument?






Poznámky redaktora
Page 245 Commissioning the HPCI 14. You can select 'Test po- larity measurement inputs' here.1 can also performed directly the REG-DP/ REG-DPA. The test can aborted any time pressing F5. Press access this function. .8. The value for Usync_phi and the polarity the channels now set and can be queried. One the Commissioning menu’s submenus 'Current injection'. The option ‘Test polarity measurement inputs’ screen shown the above figure.2 Testing directly the REG-DP/ REG-DPA The automatic polarity test for the measurement channels for the current injection de- scribed Chapter 13. Press <MENU><F3><F5><F1> <F5> access the sub menu 'Current injection'. After the test has finished successfully, the message 'Polarity test successfully completed' displays. Note: In contrast the test, current injection switched off through the WinEDC service screen following successful test.9