Petersenova cívka s regulátorem REG-DP

| Kategorie: Leták / Datasheet  |

Operating Instructions for the Petersen-Coil Regulator

Vydal: EBERLE Controls GmbH

Strana 245 z 272

Jak získat tento dokument?






Poznámky redaktora
8. . Press <MENU><F3><F5><F1> <F5> access the sub menu 'Current injection'. The option ‘Test polarity measurement inputs’ screen shown the above figure. You can select 'Test po- larity measurement inputs' here. After the test has finished successfully, the message 'Polarity test successfully completed' displays. Note: In contrast the test, current injection switched off through the WinEDC service screen following successful test.Page 245 Commissioning the HPCI 14.9. The test can aborted any time pressing F5. The value for Usync_phi and the polarity the channels now set and can be queried. One the Commissioning menu’s submenus 'Current injection'.2 Testing directly the REG-DP/ REG-DPA The automatic polarity test for the measurement channels for the current injection de- scribed Chapter 13.1 can also performed directly the REG-DP/ REG-DPA. Press access this function