Petersenova cívka s regulátorem REG-DP

| Kategorie: Leták / Datasheet  |

Operating Instructions for the Petersen-Coil Regulator

Vydal: EBERLE Controls GmbH

Strana 244 z 272

Jak získat tento dokument?






Poznámky redaktora
Une for the current injection controller and for the REG-DP/ REG-DPA must always be measured the same spot. The values for Une (Uns) the current injection controller can viewed the second line (in red). The test can stopped any time pressing the 'OFF' key. UneDPA and UneCIC160 .Page 244 Commissioning the HPCI We take care it. If the polarity this channel reversed, automatic test will detect and correct it. Current injection stays after the test has finished and must switched off pressing the 'OFF' key. The reversed polarity channel displayed under 'Polarity measurement inputs'. Current injection also switched off when you exit the service screen. In the example, Une (Uns) connected channel the current injection controller. If, for example, the phase Uen the REG-DP/ REG-DPA and Uen the current injection controller (CIC) are different, the phase the U-sync input automatically rotated until the absolute value and the phase match each other