Operating Instructions for the Petersen-Coil Regulator

Vydal: EBERLE Controls GmbH

Strana 205 z 272

Jak získat tento dokument?






Poznámky redaktora
Default value: 30° . – Phase U-Sync The value determined during commissioning testing the polarity the current and voltage channels. However, the same zero sequence voltage measured both devices. Because the current injected the PAW, the ratio 12000 V/500 for the current transformer factor (kni) can set there. Because the phase the only thing that is important U-Sync, knu can used here. The absolute value and especially the phase must the same both measurement inputs. Values increments 15° can entered. The current Ici already measured the sec- ondary side the current injection controller.: coil nominal voltage/500 power auxiliary winding (PAW) Kni 24 I2 OFF: Not used I3 OFF: Not used In the example, the coil's nominal voltage kV, the transformer's nominal value 100 V and the PAW's nominal voltage 500 V. The conversion ratio knu for the value Uns_Coil 120.Page 205 Commissioning current injection – current measurement inputs Settings: Setting Description OFF: Current measurement input not used Ici Current injected PAW - wired cabinet default current channel 1 Is Current through the P-coil (only needed for the 'Uns Uod If' algorithm) If Current through the fixed coil (only needed for the 'Uns Uod If' algorithm) Default allocation for current channels Measurement channel Default allocation and settings I1 Ici Ex. The reason for this that the synchronization voltage Usync the REG-DP/ REG-DPA may not have the same phase the synchronization voltage the current injection controller