The reason for this that the synchronization voltage Usync the REG-DP/ REG-DPA may
not have the same phase the synchronization voltage the current injection controller.
Values increments 15° can entered.
The conversion ratio knu for the value Uns_Coil 120. Because the phase the only thing that is
important U-Sync, knu can used here. The absolute value
and especially the phase must the same both measurement inputs.
Because the current injected the PAW, the ratio 12000 V/500 for the current
transformer factor (kni) can set there.: coil nominal voltage/500 power auxiliary winding
(PAW)
Kni 24
I2 OFF:
Not used
I3 OFF:
Not used
In the example, the coil's nominal voltage kV, the transformer's nominal value 100 V
and the PAW's nominal voltage 500 V. The current Ici already measured the sec-
ondary side the current injection controller.
Default value: 30°
.
– Phase U-Sync
The value determined during commissioning testing the polarity the current and
voltage channels.
However, the same zero sequence voltage measured both devices.Page 205
Commissioning current injection
– current measurement inputs
Settings:
Setting Description
OFF: Current measurement input not used
Ici Current injected PAW
- wired cabinet default current channel 1
Is Current through the P-coil (only needed for the 'Uns Uod If' algorithm)
If Current through the fixed coil (only needed for the 'Uns Uod If' algorithm)
Default allocation for current channels
Measurement
channel
Default allocation and settings
I1 Ici
Ex