Commissioning current injection
– Frequency
Settings:
Value Description Corresponds frequencies
6- Two frequencies 25Hz 75Hz
8- Two frequencies 33.8Hz 54.7Hz
10- Two frequencies 41.3Hz
8+50 Three frequencies 33.7Hz 58.8Hz 54.7Hz
6+50 Three frequencies 25Hz 75Hz
– Current
The amplitude the manual current injection set here.
.
Setting range: 100 %
Default value: 100 %
0 Measuring
Figure 136: Setup the measurement channels for current injection
The figure shows the default settings for the measurement inputs the current injection
controller for the 'Uns Ici' algorithm