Petersenova cívka s regulátorem REG-DP

| Kategorie: Leták / Datasheet  |

Operating Instructions for the Petersen-Coil Regulator

Vydal: EBERLE Controls GmbH

Strana 203 z 272

Jak získat tento dokument?






Poznámky redaktora
2Hz 10+50 Three frequencies 41.3Hz 11- Two frequencies (default) 45.3Hz 66. Current injection has three measurement channels for voltage and current.2Hz 12+50 Pure current injection Hz 11+50 Three frequencies 45.7Hz 58.3Hz 66.Page 203 Commissioning current injection – Frequency Settings: Value Description Corresponds frequencies 6- Two frequencies 25Hz 75Hz 8- Two frequencies 33.8Hz 54.7Hz 10- Two frequencies 41.3Hz 8+50 Three frequencies 33.7Hz 58.8Hz 54.7Hz 6+50 Three frequencies 25Hz 75Hz – Current The amplitude the manual current injection set here. . Setting range: 100 % Default value: 100 % 0 Measuring Figure 136: Setup the measurement channels for current injection The figure shows the default settings for the measurement inputs the current injection controller for the 'Uns Ici' algorithm