Name Description Message/Response 32 Slave missing Slave regulator not available Parallel operation deactivated BOF 'Alarm' BOF 'Alarm td' BOF 'Err_Sum' 33 CI_old_DP_FW Firmware REG-DP too old for CIC! Update firmware! If necessary 'emergency opera- tion' BOF '29:Alarm' BOF '30:Alarm_td' BOF '36:Err_Sum' BOF '64:CI_missing’ 34 CI_EEPROM_Err EEPROM error the CIC search that progress is aborted and restarted; neces- sary 'emergency operation' BOF '29:Alarm' BOF '30:Alarm_td' BOF '36:Err_Sum' BOF '64:CI_missing’ 35 CI_NoKalib Error: CIC not calibrated! necessary 'emergency opera- tion' BOF '29:Alarm' BOF '30:Alarm_td' BOF '36:Err_Sum' BOF '64:CI_missing’ 36 CI_wrongTypes Error: unsuitable CI(C) variants have been configured the CIC.Page 175 Detailed description REG-DP/ REG-DPA parameters No. If necessary 'emergency opera- tion' BOF '29:Alarm' BOF '30:Alarm_td' BOF '36:Err_Sum' BOF '64:CI_missing’ 37 CI_U1_low CIC error: Voltage too small => Check fuse A search that progress is aborted and restarted; neces- sary 'emergency operation' BOF '29:Alarm' BOF '30:Alarm_td' BOF '36:Err_Sum' BOF '64:CI_missing’