Petersenova cívka s regulátorem REG-DP

| Kategorie: Leták / Datasheet  |

Operating Instructions for the Petersen-Coil Regulator

Vydal: EBERLE Controls GmbH

Strana 174 z 272

Jak získat tento dokument?






Poznámky redaktora
Regulator moves into the predefined posi- tion. No. Name Description Message/Response 24 Hardware error Firmware not compatible with the device hardware goes into 'Error' state 25 missing One more measured values for the search algorithm are missing! Check the input functions the measurement inputs! A new search started; nec- essary 'emergency operation" BOF '29:Alarm' BOF '30:Alarm_td' BOF '36:Err_Sum' 26 blocked Current injection blocked! search that progress is aborted and restarted; neces- sary 'emergency operation' BOF '29:Alarm' BOF '30:Alarm_td' BOF '36:Err_Sum' BOF '62:CI_block' BOF '64:CI_missing’ 27 fuse trip automatic CI fuse has blown! A search that progress is aborted and restarted; neces- sary 'emergency operation' BOF '29:Alarm' BOF '30:Alarm_td' BOF '36:Err_Sum' BOF '64:CI_missing’ 28 Battery empty Battery empty more responses BOF '4:Status' BOF '36:Err_Sum' BOF '58:Battery empty' 29 SearchErrUmax Search unsuccessful! Une Umax could not be kept Search aborted. The regulator stays in 'AUTO' mode! BOF 'Alarm' BOF 'Alarm td' BOF 'Err_Sum' 30 User error User-defined error (#: <No>) Is created background program - goes into 'Error' state - goes into MAN state BOF 'Error' BOF 'Error td' BOF 'Err_Sum' 31 User alarm User-defined alarm (#: <No>) Is created background program BOF 'Alarm' BOF 'Alarm td' BOF 'Err_Sum' .Page 174 Detailed description REG-DP/ REG-DPA parameters We take care it