No.Page 176 Detailed description REG-DP/ REG-DPA parameters
We take care it. Name Description Message/Response
38 CI_I13_low CIC error: Uns voltage too high to
search! (if necessary, check fuse Q1)
AUTO: search that pro-
gress aborted and restarted;
If necessary 'emergency opera-
tion'
MAN: switched off
BOF '29:Alarm'
BOF '30:Alarm_td'
BOF '36:Err_Sum'
BOF '64:CI_missing’
39 CI_L1_low CIC error: Voltage Usync (L1) missing search that progress is
aborted and restarted; neces-
sary 'emergency operation'
BOF '29:Alarm'
BOF '30:Alarm_td'
BOF '36:Err_Sum'
BOF '64:CI_missing’
40 CI_StatusErrThy Error: Control electronics are
defective
A search that progress is
aborted and restarted; neces-
sary 'emergency operation'
BOF '29:Alarm'
BOF '30:Alarm_td'
BOF '36:Err_Sum'
BOF '64:CI_missing’
41 CI_Temp Error: Control electronics are too
hot
A search that progress is
aborted and restarted; neces-
sary 'emergency operation'
BOF '29:Alarm'
BOF '30:Alarm_td'
BOF '36:Err_Sum'
BOF '64:CI_missing’
42 CI_Ici_ON error: Injection current too
small! Check fuse F1!
A search that progress is
aborted and restarted; neces-
sary 'emergency operation'
BOF '29:Alarm'
BOF '30:Alarm_td'
BOF '36:Err_Sum'
BOF '64:CI_missing’
43 CI_Ici_OFF Error: Control electronics are
defective! Leakage current thyris-
tors too big
A search that progress is
aborted and restarted; neces-
sary 'emergency operation'
BOF '29:Alarm'
BOF '30:Alarm_td'
BOF '36:Err_Sum'
BOF '64:CI_missing’