Stop response from the slave regulator
Standby position The slave regulator adjusts its
coil the set standby position
Tuning pos when Une<Umin, the slave adjusts
its coil its last known tuning point
Fixed position,
when slave
in Ampere 100A Predefined position for the slave coil when the
option 'Fixed position' selected the Move
slave coil parameter
.Page 125
Detailed description REG-DP/ REG-DPA parameters
Parameters Range Factory set-
tings
Description
Parallel pro-
gram
OFF;
Mas-
ter/Slave;
OFF: Type parallel regulation used
Active OFF:
ON
BB connec-
tion
OFF: Type activation used activate the parallel
program
ON always active
BB coupling feedback from busbar coupling
Slave . the slave that connected the master in
the E-LAN
Move slave
coil
NO
Tune
fixed positi-
on
NO the master regulator should able adjust
the slave..
No The master does not perform any action on
the slave
Tune When the master regulator's adjustment
range longer sufficient, the slave coil ad-
justed accordingly
fixedPosition The slave coil adjusted the
value that set the Fixed position parameter
when the slave defined
SlavePosition
at Umin
Stop
Standby
position
Tuning pos
Stop Position the slave when the zero sequence
voltage Une Umin