Petersenova cívka s regulátorem REG-DP

| Kategorie: Leták / Datasheet  |

Operating Instructions for the Petersen-Coil Regulator

Vydal: EBERLE Controls GmbH

Strana 125 z 272

Jak získat tento dokument?






Poznámky redaktora
. Stop response from the slave regulator Standby position The slave regulator adjusts its coil the set standby position Tuning pos when Une<Umin, the slave adjusts its coil its last known tuning point Fixed position, when slave in Ampere 100A Predefined position for the slave coil when the option 'Fixed position' selected the Move slave coil parameter .Page 125 Detailed description REG-DP/ REG-DPA parameters Parameters Range Factory set- tings Description Parallel pro- gram OFF; Mas- ter/Slave; OFF: Type parallel regulation used Active OFF: ON BB connec- tion OFF: Type activation used activate the parallel program ON always active BB coupling feedback from busbar coupling Slave . the slave that connected the master in the E-LAN Move slave coil NO Tune fixed positi- on NO the master regulator should able adjust the slave.. No The master does not perform any action on the slave Tune When the master regulator's adjustment range longer sufficient, the slave coil ad- justed accordingly fixedPosition The slave coil adjusted the value that set the Fixed position parameter when the slave defined SlavePosition at Umin Stop Standby position Tuning pos Stop Position the slave when the zero sequence voltage Une Umin