MAN mode
takes precedence.
0 Earth fault behaviour
– Slave blocked
– Only the master readjusted according the setting the menu:
. slave
that MAN mode cannot adjusted the master. soon this information longer transmitted, the slave becomes inde-
pendent regulator again.
If the slave readjusted the master, the slave will display message indicating that is
being positioned the master: 'Positioning slave'
0 End parallel operation
Master
The regulator leaves the 'Master' state and starts the search process after the long delay
time the trigger threshold was violated the switching operation.Page 126 Detailed description REG-DP/ REG-DPA parameters
We take care it.
Slave AUTO mode
Slave leaves its state and starts its search process after the short delay time.
Figure 89: Setting the coupling function binary input 12
0 Behaviour with active parallel regulation with communication
The master detects the parallel operation, displays its display and informs the slave
regulator that now its slave.
The slave shows its 'slave state' its status bar. However, the master not allowed to
adjust the slave even this option active and the 'Slave' not displayed.
The slave also activated when MAN mode.
The slave sends the current position the coil and any active fixed coils the master
through the E-LAN. The slave must AUTO mode. The slave receives this information cycles during parallel
operation