Petersenova cívka s regulátorem REG-DP

| Kategorie: Leták / Datasheet  |

Operating Instructions for the Petersen-Coil Regulator

Vydal: EBERLE Controls GmbH

Strana 123 z 272

Jak získat tento dokument?






Poznámky redaktora
[R:10] Resistor control blocked; temperature too high (R:10) Resistor control blocked active Locking parameter (see description for the Locking parameter) . If desired, the temperature the thermal replica can also output analogue output or the serial connection the SCADA system. The asterisk displayed during the whole switch-on time. R:0 The resistor too hot The resistor cannot switched again until the remain- ing residual current increases have value least The relay also sends a notification that the limit temperature has been reached. Resistor control works whether the regulator MAN AUTO mode! The following display options are available: Display Description R:10 Resistor control active, and residual current increases are still possible full zero sequence voltage *R:10 The residual current increase progress.Page 123 Detailed description REG-DP/ REG-DPA parameters 0 From the regulator's menu 0 Impulse from the binary input function R_auto_off 0 Second impulse from the binary input function R_auto_onoff 0 Turn-off command from the SCADA system When resistor control active, the regulator displays the remaining number permissible full impulse sequences for saturated earth fault the top right corner