Petersenova cívka s regulátorem REG-DP

| Kategorie: Leták / Datasheet  |

Operating Instructions for the Petersen-Coil Regulator

Vydal: EBERLE Controls GmbH

Strana 123 z 272

Jak získat tento dokument?






Poznámky redaktora
Page 123 Detailed description REG-DP/ REG-DPA parameters 0 From the regulator's menu 0 Impulse from the binary input function R_auto_off 0 Second impulse from the binary input function R_auto_onoff 0 Turn-off command from the SCADA system When resistor control active, the regulator displays the remaining number permissible full impulse sequences for saturated earth fault the top right corner. R:0 The resistor too hot The resistor cannot switched again until the remain- ing residual current increases have value least The relay also sends a notification that the limit temperature has been reached. [R:10] Resistor control blocked; temperature too high (R:10) Resistor control blocked active Locking parameter (see description for the Locking parameter) . The asterisk displayed during the whole switch-on time. If desired, the temperature the thermal replica can also output analogue output or the serial connection the SCADA system. Resistor control works whether the regulator MAN AUTO mode! The following display options are available: Display Description R:10 Resistor control active, and residual current increases are still possible full zero sequence voltage *R:10 The residual current increase progress