Petersenova cívka s regulátorem REG-DP

| Kategorie: Leták / Datasheet  |

Operating Instructions for the Petersen-Coil Regulator

Vydal: EBERLE Controls GmbH

Strana 105 z 272

Jak získat tento dokument?






Poznámky redaktora
Default setting: 30% 0 Uerd message delay: Transient earth fault An earth fault identified when the absolute value the zero sequence voltage Une is higher than the threshold value set for Uerd.3. – The delayed earth fault message.2. Regulation always stops when earth fault occurs because the same zero sequence volt- age would measured across the coil's whole adjustment range making regulation impossible. 11. also not certain whether older coils can moved when earth fault oc- curs because the drive unit not always equipped overcome the high magnetic forces.1 Earth fault 0 Uerd threshold If the set threshold exceeded, the coil movements and the current injection (if used) are suppressed.Page 105 Detailed description REG-DP/ REG-DPA parameters Four parameters determine the regulator's behaviour when earth fault occurs. The earth fault must also occur during the whole delay time. The earth fault generates two types messages: – The immediate earth fault message This message displayed soon the earth fault has been identified. Une Transient earth fault Message delay T_V T_EW t T_EW Transient earth fault time T_V Uerd message delay Figure 76: Time behaviour the earth fault . The below figure displays the time behaviour for the regulator. This message displayed after the set delay time. This value relates the nominal value the coil's nominal voltage