Petersenova cívka s regulátorem REG-DP

| Kategorie: Leták / Datasheet  |

Operating Instructions for the Petersen-Coil Regulator

Vydal: EBERLE Controls GmbH

Strana 105 z 272

Jak získat tento dokument?






Poznámky redaktora
Regulation always stops when earth fault occurs because the same zero sequence volt- age would measured across the coil's whole adjustment range making regulation impossible. The earth fault generates two types messages: – The immediate earth fault message This message displayed soon the earth fault has been identified. – The delayed earth fault message.3.2. The earth fault must also occur during the whole delay time. This value relates the nominal value the coil's nominal voltage. 11. This message displayed after the set delay time. Default setting: 30% 0 Uerd message delay: Transient earth fault An earth fault identified when the absolute value the zero sequence voltage Une is higher than the threshold value set for Uerd. Une Transient earth fault Message delay T_V T_EW t T_EW Transient earth fault time T_V Uerd message delay Figure 76: Time behaviour the earth fault . The below figure displays the time behaviour for the regulator. also not certain whether older coils can moved when earth fault oc- curs because the drive unit not always equipped overcome the high magnetic forces.1 Earth fault 0 Uerd threshold If the set threshold exceeded, the coil movements and the current injection (if used) are suppressed.Page 105 Detailed description REG-DP/ REG-DPA parameters Four parameters determine the regulator's behaviour when earth fault occurs