Petersenova cívka s regulátorem REG-DP

| Kategorie: Leták / Datasheet  |

Operating Instructions for the Petersen-Coil Regulator

Vydal: EBERLE Controls GmbH

Strana 104 z 272

Jak získat tento dokument?






Poznámky redaktora
You should choose value that corresponds the desired tuning point the grid's most frequent switching state. min, error message displayed after about full cycles the regulator still hasn't reached tuned state. In addition monitoring the maximum number cycles, the motor runtime summed. The regulator the Tuned state, this counter reset maximum zero.Page 104 Detailed description REG-DP/ REG-DPA parameters We take care it.2 Earth fault, Umin, Umax . This triggers additional monitoring ensure the coil doesn’t move too often. Default setting: Standby position 0 Standby position: If the parameter End position cancel set Standby position, enter the corresponding value here.3. Default setting: A 11. Default setting: min 0 End position cancel: If the number search cycles the specified motor runtime exceeded, the P-coil ad- justed predefined value. For coil runtime ca. TuningP The P-coil adjusted the last valid tuning point. There are two options: Parameters Description Standby posi- tion The P-coil adjusted defined value, which set the below parameter. The counter incremented soon the coil moved