Petersenova cívka s regulátorem REG-DP

| Kategorie: Leták / Datasheet  |

Operating Instructions for the Petersen-Coil Regulator

Vydal: EBERLE Controls GmbH

Strana 104 z 272

Jak získat tento dokument?






Poznámky redaktora
Default setting: A 11. In addition monitoring the maximum number cycles, the motor runtime summed.2 Earth fault, Umin, Umax . This triggers additional monitoring ensure the coil doesn’t move too often. The counter incremented soon the coil moved. Default setting: Standby position 0 Standby position: If the parameter End position cancel set Standby position, enter the corresponding value here.3. You should choose value that corresponds the desired tuning point the grid's most frequent switching state. TuningP The P-coil adjusted the last valid tuning point. min, error message displayed after about full cycles the regulator still hasn't reached tuned state.Page 104 Detailed description REG-DP/ REG-DPA parameters We take care it. For coil runtime ca. There are two options: Parameters Description Standby posi- tion The P-coil adjusted defined value, which set the below parameter. Default setting: min 0 End position cancel: If the number search cycles the specified motor runtime exceeded, the P-coil ad- justed predefined value. The regulator the Tuned state, this counter reset maximum zero