the regula-
tor cannot find valid resonance curve within the set search cycles, the REG-DP places the
P-coil standby position.
Default setting: inactive)
0 Positioning tolerance:
This parameter used set the tolerance for the positioning the P-coil. The percent
value related the P-coil's Imax.
A search cycle consists the following regulator functions:
Starting the search, calculating the resonance curve, moving towards the end position and
comparing the reached position with the calculated position. This
means that the default setting should not decreased combination with current
injection.
Default setting: 10
Note:
With current injection, repositioning search will consist least two search cycles.4 Cancelling the search
0 Max search cycles
This parameter describes the maximum number consecutive search cycles.5%).
If the zero sequence voltage the end position does not correspond the calculated val-
ue curve could not determined for other reasons, the cycle considered have
completed unsuccessfully and new search cycle started.: 1*20% %
Note:
It can make sense disable this function for very small zero sequence voltages (value <
0.
0 Motor runtime max:
.1.Page 103
Detailed description REG-DP/ REG-DPA parameters
Check resonance curve (factor) Une tolerance
Ex.5% inactive)
Positioning tolerance (%)* Imax
11.
Note:
When the coil backlash the overrun too big, increasing this value will prevent oscilla-
tions during positioning. The type standby position set the parameter 'End posi-
tion cancel'.
Default setting: 1.3