Petersenova cívka s regulátorem REG-DP

| Kategorie: Leták / Datasheet  |

Operating Instructions for the Petersen-Coil Regulator

Vydal: EBERLE Controls GmbH

Strana 106 z 272

Jak získat tento dokument?






Poznámky redaktora
If the regulator searching for new resonance point when the earth fault occurs, the search immediately aborted. In terms the duration the earth fault the following applies: – terd TEW If the regulator was tuned when the earth fault occurred and the zero sequence voltage returned its initial value within the transient earth fault time, as- sumed that the P-coil successfully extinguished the arc. The P-coil does not have readjusted. new search process always started the end - earth fault even the earth fault time smaller than the set transient earth fault time TEW.Page 106 Detailed description REG-DP/ REG-DPA parameters We take care it. Default settings: 7s TEW 7s . This probably happened without adjusting the P-coil and without switching off the line sections. – terd TEW If the earth fault lasts longer than the transient earth fault time, might neces- sary switch off the lines order solve the earth fault. ensure that the P- coil set the right value, search started even the zero sequence voltage has returned its initial value