. the example, the potenti- ometer has value 4. Coil backlash The hysteresis, caused the mechanical backlash between the coil's iron core, air gap and potentiometer determined.4%, which corresponds coil current 200A. Imin Coil's compensation current the lower end switch position. the example, the po- tentiometer has value 95. Overrun The time that the drive continues run after the stop command. Check the wiring the non-linearity the potentiometer characteristic too high 2%). Imax The coil's compensation current the upper end switch position.Page 79 Commissioning The calibration results are displayed the next screens the 'Coil calibration' menu, which are accessed pressing <F1>. Operating time The time needed move the coil from the lower the upper end switch. If only lines are used, the non-linearity can increased.5%, which corresponds coil current A