Petersenova cívka s regulátorem REG-DP

| Kategorie: Leták / Datasheet  |

Operating Instructions for the Petersen-Coil Regulator

Vydal: EBERLE Controls GmbH

Strana 79 z 272

Jak získat tento dokument?






Poznámky redaktora
Check the wiring the non-linearity the potentiometer characteristic too high 2%). Overrun The time that the drive continues run after the stop command.4%, which corresponds coil current 200A.Page 79 Commissioning The calibration results are displayed the next screens the 'Coil calibration' menu, which are accessed pressing <F1>. . Operating time The time needed move the coil from the lower the upper end switch. the example, the po- tentiometer has value 95. Imax The coil's compensation current the upper end switch position.5%, which corresponds coil current A. the example, the potenti- ometer has value 4. Imin Coil's compensation current the lower end switch position. If only lines are used, the non-linearity can increased. Coil backlash The hysteresis, caused the mechanical backlash between the coil's iron core, air gap and potentiometer determined