It therefore meaningful stimulate the current injection calculate/check the grid pa-
rameters regular intervals. Example every min
Default setting: min inactive)
0 New search after positioning
If the checkbox for this parameter checked, the REG-DP/ REG-DPA will perform control
measurement after successful tuning check the resonance curve again.Page 201
Commissioning current injection
This where the basic parameters are set that are used determine the grid parameters
by including current injection the calculation. stays alarm state for more than 60s, the regulator will go
into error state and switch MAN.
0 algorithm
Settings:
Uns Ici: Default algorithm calculate the grid parameters
Uns Uod If: Extended algorithm, this parameter only used with the ENEL feature
and useful combination with EDC-Sys
Default setting: Uns Ici
0 cycl. the value the
same, the coil will stay this position. Stimulate all
If the zero sequence voltage the resonance curve extremely flat, relative change in
the zero sequence voltage that caused switching operation will have very little im-
pact the Une.
Default setting: YES
.
Default setting: active
0 Emergency operation 'Move coil'
If the communication the current injection controller fails,
the REG-DP/ REG-DPA can switch classic regulation moving the coil
Settings:
YES: The REG-DP/ REG-DPA allowed move the coil determine the res-
onance curve current not injected.
NO: The REG-DP/ REG-DPA not allowed move the coil determine the
resonance curve current not injected The regulator goes into alarm
state