Default setting: active
0 Emergency operation 'Move coil'
If the communication the current injection controller fails,
the REG-DP/ REG-DPA can switch classic regulation moving the coil
Settings:
YES: The REG-DP/ REG-DPA allowed move the coil determine the res-
onance curve current not injected. the value the
same, the coil will stay this position.
0 algorithm
Settings:
Uns Ici: Default algorithm calculate the grid parameters
Uns Uod If: Extended algorithm, this parameter only used with the ENEL feature
and useful combination with EDC-Sys
Default setting: Uns Ici
0 cycl. Stimulate all
If the zero sequence voltage the resonance curve extremely flat, relative change in
the zero sequence voltage that caused switching operation will have very little im-
pact the Une. stays alarm state for more than 60s, the regulator will go
into error state and switch MAN.
NO: The REG-DP/ REG-DPA not allowed move the coil determine the
resonance curve current not injected The regulator goes into alarm
state. Example every min
Default setting: min inactive)
0 New search after positioning
If the checkbox for this parameter checked, the REG-DP/ REG-DPA will perform control
measurement after successful tuning check the resonance curve again.
It therefore meaningful stimulate the current injection calculate/check the grid pa-
rameters regular intervals.Page 201
Commissioning current injection
This where the basic parameters are set that are used determine the grid parameters
by including current injection the calculation.
Default setting: YES