Petersenova cívka s regulátorem REG-DP

| Kategorie: Leták / Datasheet  |

Operating Instructions for the Petersen-Coil Regulator

Vydal: EBERLE Controls GmbH

Strana 201 z 272

Jak získat tento dokument?






Poznámky redaktora
It therefore meaningful stimulate the current injection calculate/check the grid pa- rameters regular intervals. Example every min Default setting: min inactive) 0 New search after positioning If the checkbox for this parameter checked, the REG-DP/ REG-DPA will perform control measurement after successful tuning check the resonance curve again.Page 201 Commissioning current injection This where the basic parameters are set that are used determine the grid parameters by including current injection the calculation. stays alarm state for more than 60s, the regulator will go into error state and switch MAN. 0 algorithm Settings: Uns Ici: Default algorithm calculate the grid parameters Uns Uod If: Extended algorithm, this parameter only used with the ENEL feature and useful combination with EDC-Sys Default setting: Uns Ici 0 cycl. the value the same, the coil will stay this position. Stimulate all If the zero sequence voltage the resonance curve extremely flat, relative change in the zero sequence voltage that caused switching operation will have very little im- pact the Une. Default setting: YES . Default setting: active 0 Emergency operation 'Move coil' If the communication the current injection controller fails, the REG-DP/ REG-DPA can switch classic regulation moving the coil Settings: YES: The REG-DP/ REG-DPA allowed move the coil determine the res- onance curve current not injected. NO: The REG-DP/ REG-DPA not allowed move the coil determine the resonance curve current not injected The regulator goes into alarm state