Regulator moves into the predefined posi- tion. Regulator moves into the predefined posi- tion.Page 172 Detailed description REG-DP/ REG-DPA parameters We take care it. The regulator stays in 'AUTO' mode! BOF '>n_Search' BOF 'Alarm' BOF 'Alarm td' BOF 'Err_Sum' 9 SearchTime Search unsuccessful! Maximum motor runtime exceeded Search aborted. Name Description Message/Response 8 Search Number Number allowed search cycles exceeded; search aborted. No. Regulator displays error Search aborted. The regulator stays in 'AUTO' mode! BOF '>T_MotOn' BOF 'Alarm' BOF 'Alarm td' BOF 'Err_Sum' 10 Positioning Target position for tuning point not reached (check positioning toler- ance) goes into 'Error' state goes into 'MAN' state BOF 'Error' BOF 'Error td' BOF 'Err_Sum' 11 Endswitch Low End switch 'Lower' not found! 12 Endswitch High End switch 'Higher' not found! 13 Endswitch Both Check end switch; both are 'ON' goes into MAN state - goes into 'Error' state BOF 'Error' BOF 'Error td' BOF 'Err_Sum' 14 Current injection not available search that progress is aborted and restarted; neces- sary 'emergency operation' BOF '29:Alarm' BOF '30:Alarm_td' BOF '36:Err_Sum' BOF '64:CI_missing’ 15 error Current injection error message With error number (#: <No>) - goes into 'Error' state - goes into MAN state BOF '34:Error' BOF '35:Error_td' 'BOF '36:Err_Sum' BOF '63:CI_Error'