Petersenova cívka s regulátorem REG-DP

| Kategorie: Leták / Datasheet  |

Operating Instructions for the Petersen-Coil Regulator

Vydal: EBERLE Controls GmbH

Strana 171 z 272

Jak získat tento dokument?






Poznámky redaktora
Page 171 Detailed description REG-DP/ REG-DPA parameters 11. Eberle.7.2. 2 CoilDirection Coil moving the wrong direction stops coil movement - goes into MAN state - goes into 'Error' state - BOF 'E:Dir' incoming - BOF 'Error' incoming - BOF 'Error td' incoming - BOF 'Err_Sum' incoming 3 CoilNoMoving Coil not moving stops coil movement - goes into MAN state - goes into 'Error' state - BOF 'E:Move' incoming - BOF 'Error' incoming - BOF 'Error td' incoming - BOF 'Err_Sum' incoming 4 Pot Potentiometer: Cable break stops coil movement - goes into MAN state - goes into 'Error' state - BOF 'PotError' incoming - BOF 'Error' incoming - BOF 'Error td' incoming - BOF 'Err_Sum' incoming 5 Pot Potentiometer: Cable break stops coil movement - goes into MAN state - goes into 'Error' state - BOF 'PotError' incoming - BOF 'Error' incoming - BOF 'Error td' incoming - BOF 'Err_Sum' incoming 6 Pot slider Potentiometer: Cable break slider contact - stops coil movement - goes into MAN state - goes into 'Error' state - BOF 'PotError' incoming - BOF 'Error' incoming - BOF 'Error td' incoming - BOF 'Err_Sum' incoming 7 DeviceStatus Device status; internal ERROR BOF '4:Status' - BOF 'Err_Sum' . Name Description Message/Response 1 InternError The error number written the logbook and must evaluated by A.3 Error messages No