This means that the coil must successfully calibrated during
commissioning.
Default setting: 0A
– I_max
Simulated position for the upper end switch.Page 154 Detailed description REG-DP/ REG-DPA parameters
We take care it.
The regulator displays ??? behind Ipos/Icomp. The regulator generates an
error message soon the smallest gap occurs the adjustment
range.
With gaps Default setting: Gaps the position feedback are accepted the
value the Pot gaps max length parameter.
CAUTION! The end switch information MUST sent the REG-DP/
REG-DPA.
Default setting: 9999A
0 Potentiometer
You can set the potentiometer's properties here. combination both pot and end switch does not
make sense.
This makes possible limit the coil range and stop the coil before the actual end posi-
tion. This means that the coil must successfully calibrated during
commissioning. The runtime
was determined during the automatic coil calibration. error not generated
until the gaps exceed the value.
.
This setting only recommended the potentiometer needs servic-
ing.
The coil's total runtime used estimate its position.
The drive stops when the coil reaches the value that set for I_min I_max.
– Pot hat gaps
Setting Description
Without gaps The potentiometer adopted ideal. The decision derived from the potentiome-
ter's position.
– Active
Software end switch function active
Default setting: inactive
– I_min
Simulated position for the lower end switch. The decision derived from the potentiome-
ter's position.
No Pot potentiometer does not have connected this setting used