. the potenti-
ometer does not change for more than (depends the coil
speed), the value used end switch position (Imin Imax).Page 153
Detailed description REG-DP/ REG-DPA parameters
11.2.
Default setting: 200A
– End switch type
The following settings are possible:
Setting Description
Normally open
contact (NOC)
Normally open contact: The contact closes when the position reached
Normally closed
contact (NCC)
Normally closed contact: The contact opens when the position reached
Not connected End switch information not available.
Default setting: 20A
– I_min (in A)
Current the coil the upper end switch position.
0 Software end switches
If end switches are available their function unreliable, the regulator can work with
software end switches.4.2 Petersen Coil
11.
The end switch information determined during calibration.1 Coil data
Figure 99: Coil data menu
0 Petersen coil
– I_min (in A)
Current value the coil the lower end switch.4